Configuring a Modbus Plus Network in Modsoft with Peer Cop
248
870USE10110 July 2004
Next Step Complete the configuration by creating a Peer Cop screen from the supervisor that
accesses node 3 and defines the references for that node.
5 Type the value 10 in the LEN column of the GLOBAL OUTPUT field to indicate the
number of registers to be sent. Push <Enter>. The REFERENCE field is completed
automatically and the cursor moves to the TYPE column.
6 With the TYPE column of the GLOBAL OUTPUT filed set to BIN, push <Enter> twice.
The Peer Cop screen should like this:
Step Action
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 17 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
DelNode
SPECIFIC INPUT 400001 -400008 8 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL OUTPUT 400033-400042 10 BIN
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 17 OF 2000WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
DelNode
SPECIFIC INPUT 400001 -400008 8 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL OUTPUT 400033-400042 10 BIN