Configuring a Modbus Plus Network in Modsoft with Peer Cop
870USE10110 July 2004 239
Specifying References for Input and Output Data on a Modbus Supervisory
Network with Momentum Components (Using Modsoft)
Overview We will now set up the 171 CCS 760 00 Momentum M1 CPU at Modbus Plus
address 2. This device will:
send eight 4x registers of specific output to the supervisory computer at Modbus
Plus address 1.
receive five 4x registers of global input from the supervisory computer. These
registers are the first five registers in a 10-register block broadcast by the
supervisor.
Defining the
Specific Output
The following table describes how to define the specific output in Peer Cop.
Step Action
1 Move the cursor to the REFERENCE column of the SPECIFIC OUTPUT field with
the cursor arrow keys.
2 In the REFERENCE column of the SPECIFIC OUTPUT field, type the value
400016. Push <Enter>.
Result: The cursor moves into the LEN column of the SPECIFIC OUTPUT field.
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 1 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
SPECIFIC INPUT -
SPECIFIC OUTPUT 400016- BIN
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
F2
Timeout
Access to Node : 1
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode