I/O Mapping an I/O Bus Network
212
870USE10110 July 2004
2 Move the cursor onto the desired model number and push <Enter>.
Result: The module type and its description are displayed on the I/O map screen.
The cursor is positioned so that you can assign the appropriate state RAM
reference(s) to the unit.
Example: If you select a 170 ADI 350 00 32-point input base, the screen will look
like this.
3 Enter the desired reference number–in this case a 3x register (300020), which will
be the first of two contiguous input registers for the 32-bit input base. The second
register is automatically assigned.
4 Move the cursor to the Module column opposite NODE 02 and push <Shift> <?>.
Result: The base/module selection popup appears again over the I/O map screen.
5 Continue to select and map modules one after the other. You must enter the
modules in contiguous node slots on the screen, e.g. you cannot enter a module in
slot 7 if you have not filled slot 6.
Step Action
F1
F2
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Type: IOBUS
MOMENTUM
Drop: 1 Available: 233
Used IO Points : 0 of 2048
PAGE
1 01 170 ADI 350 00 32 dg 24vdc inp
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
Module Input Ref Output Ref Description
NODE
Utility
ClrDrop
Drop Quit
F1
F2
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Type: IOBUS
Insert
MOMENTUM
Drop: 1 Available: 196
Used IO Points : 160 of 2048
PAGE
1 01 170 ADI 350 00 300010-300011 32 dg 24vdc inp
1 02 170 ADI 340 00 300012-300012 16 dg 24vdc inp
1 03 170 AMM 090 00 300013-300017 400010-400014 4i/2o an1 4i/2o dg
1 04 170 ADO 540 50 400015-400015 16 dg 115vac out
1 05 170 ADM 690 50 300018-300018 400016-400016 10in+8out 115vac
106
107
108
109
110
111
112
113
114
115
116
Module Input Ref Output Ref Description