Configuring an M1 CPU with Modsoft
870USE10110 July 2004 201
Changing the Delay Parameter on Modbus Communication Ports for Momentum
Components Using Modsoft
Overview The default value for the delay parameter is 10 ms. This value is appropriate for most
Momentum applications.
However, if you use baud rates lower than 4800, you should adjust the delay timing.
Delay Timing If you use baud rates lower than 4800, adjust the delay timing as indicated in the
following table:
Valid Delay
Values
The delay must always be a value between 10 and 200 ms, expressed in 10 ms
increments.
Procedure From the port editor screen, perform the steps in the following table to change the
delay parameter:
Baud Rate Delay (in ms)
2400 20
1200 30
600 50
300 100
Step Action
1 Place the cursor on the current delay entry for the Modbus port.
2 Type a new value in the range 10 ... 200 ms, using 10 ms increments. Push
<Enter>.
Result: The port editor screen is updated with the delay you have specified.