I/O Mapping an I/OBus Network with Modsoft
186
870 USE 101 00 V.2.2
Editing the I/OBus I/O Map,
Continued
Procedure,
Continued
Continued on next page
Step Action
2 Move the cursor onto the desired model number and push
<Enter>
.
Result:
The module type and its description are displayed on the I/O Map screen.
The cursor is positioned so that you can assign the appropriate state RAM
reference(s) to the unit.
Example:
If you select a 170 ADI 350 00 32-point input base, the screen will look
like this:
3 Enter the desired reference number–in this case a 3
x
register (300020), which will
be the first of two contiguous input registers for the 32-bit input base. The second
register is automatically assigned.
4 Move the cursor to the Module column opposite NODE 02 and push
<Shift>
<?>
.
Result:
The base/module selection popup appears again over the I/O Map
screen.